Fronius
IG Plus |
5.0-1UNI |
6.0-1UNI |
7.5-1UNI |
Input
data |
|
Recommended PV-Power (Wp) |
4250-5750 |
5100-6900 |
6350-8600 |
MPPT-Voltage
range |
230 - 500 V |
Max.
Input voltage range
(at 1000 W/m² 14°F (-10°C)
in open circuit operation) |
600 V |
Nominal
Input Current |
13.8 A |
16.6 A |
20.7 A |
Max.
usable Input Current |
23.4 A |
28.1 A |
35.1 A |
Admissible conductor size (DC) |
No. 14-6 AWG |
Output
data |
|
Nominal
output power (PAC nom) Watts |
5000 |
6000 |
7500 |
Max.
cont. output power
104°F (40°C) 208 V / 240 V / 277 V |
5000 |
6000 |
7500 |
Nominal
AC output voltage |
208 V / 240 V / 277 V |
Operating AC voltage range
208 V
240 V
277 V |
183 - 229 V (-12 / +10 %)
211 - 264 V (-12 / +10%)
244 - 305 V (-12 / +10 %) |
Nominal
output current (A)
208 V
240 V
277 V |
24.0 A
20.8 A
18.1 A |
28.8 A
25.0 A
21.7 A |
36.1 A
31.3 A
27.1 A |
Max.
output current (A)
208 V
240 V
277 V |
27.3 A
23.7 A
20.5 A |
32.8 A
28.4 A
24.6 A |
37.0 A
35.5 A
30.7 A |
Admissible conductor size (AC) |
No. 14 - 4 AWG |
Max.
continuous utility back feed current |
0 A |
Nominal
frequency |
60 Hz |
Operating frequency range |
59.3 - 60.5 Hz |
Total
harmonic distortion |
< 3 % |
Power
factor |
1 |
General data |
|
Max.
Efficiency |
96.20% |
CEC
Efficiency
208 V
240 V
277 V |
95.5 %
95.5 %
95.0 % |
95.5 %
95.0 %
95.0 % |
95.0 %
95.5 %
95.0 % |
Consumption in standby (night) |
< 1 W |
Consumption during operation |
15 W |
Cooling |
Controlled forced ventilation, variable fan speed |
Enclosure Type |
NEMA 3R |
Unit
Dimensions (W x H x D) |
17.1 x 36.4 x 9.6. in. |
Inverter
Weight |
57 lbs. (26 kg) |
Wiring
Compartment Weight |
26 lbs. (12 kg) |
Admissible ambient operating temperature |
-4 ... 122°F (-20 ... + 50°C) |
Compliance |
UL 1741-2005, IEEE1547-2003, IEEE 1547.1, ANSI/IEEE C62.41, FCC Part 15 A&B,
NEC Article 690, C22. 2 No. 107.1-01 (Sept. 2001) |
Safety
equipment |
|
Ground
fault protection |
Internal GFDI (Ground Fault Detector/Interrupter); in accordance with UL
1741-2005 and NEC Art. 690 |
DC
reverse polarity protection |
Internal diode |
Islanding protection |
Internal; in accordance with UL 1741-2005, IEEE 1547-2003 and NEC |
Over
temperature |
Output power de-rating / active cooling |